RE 22
The RE 22 contactor starter is manufactured in a flameproof housing and provides control and power supply of one motor with maximum power of 355 kW (1000 V) or simultaneous control and power supply of two motors with maximum power of 160 kW (1000 V) each.
The apparatus is equipped with safety devices protecting against: short-circuits, load asymmetry, overload, main channel low insulation resistance, short circuits, high resistance and control circuit in¬terruptions, high earthing resistance, incorrect supply voltage phase sequence (option).
The apparatus is equipped with safety devices protecting against: short-circuits, load asymmetry, overload, main channel low insulation resistance, short circuits, high resistance and control circuit in¬terruptions, high earthing resistance, incorrect supply voltage phase sequence (option).
Technical data
| Item | |
Rated voltage Un |
V |
nominal dc |
A |
total input current ar R, S, T contactors |
A |
making capacity at Ue=500V in utilization category AC3 |
kW |
making capacity at Ue=1000V in utilization category AC3 |
kW |
overload protection adjustment range |
A |
1-phase auxiliary voltage |
V |
main channel BZU adjusment resistance |
kOhm |
dimensions with inlets (width x height x depth) |
mm |
Weight |
kg |
degree of protection of enclosure |
- |
certified with mark |
- |
certificate number |
- |
| Item | RE 22 | |
Rated voltage Un |
V |
500, 1000, 50 Hz |
nominal dc |
A |
1x250 or 2x125 |
total input current ar R, S, T contactors |
A |
≤ 400* |
making capacity at Ue=500V in utilization category AC3 |
kW |
160 or 2x90 |
making capacity at Ue=1000V in utilization category AC3 |
kW |
355 or 2x160 |
overload protection adjustment range |
A |
from 20 to 396 ** |
1-phase auxiliary voltage |
V |
24, 42, 50 Hz |
main channel BZU adjusment resistance |
kOhm |
50 |
dimensions with inlets (width x height x depth) |
mm |
1000 x 810 x 570 |
Weight |
kg |
330 |
degree of protection of enclosure |
- |
IP 54 |
certified with mark |
- |
CE 1453, I M2 EEx d [ia] I |
certificate number |
- |
KDB 06ATEX095X |
* load capacity grip of loop-through I = 400 A - Iload
** On customer request, the starters can be equipped with different than standard overload protection range
Information about types are available in catalogue.
Diagram
Application
The contactor starters are designed for controlling and powering electrical engines of mining driver systems from three-phase supply networks with the transformer's insulated neutral point on the secondary side.
The contactor starters meet to requirements of the European Directive 94/9/EC (ATEX) for equipment in group I, category M2, and can be used in methane and coal dust exsplosion hazardous areas of underground mines.
The contactor starters meet to requirements of the European Directive 94/9/EC (ATEX) for equipment in group I, category M2, and can be used in methane and coal dust exsplosion hazardous areas of underground mines.
Design
The contactor starters are made in a flameproof housing. Devices are fitted with protective devices against:
- short circuits,
- load asymmetry,
- overload,
- main channel low insulation resistance,
- short circuits, high resistance and control circuit interruptions,
- high earthing resistance
- incorrect power voltage phase sequence (optionally).
The starters can optionally be fitted with phase sequence control system which is specifically important when powering pumps as incorrect engine rotation may cause damage to the device.
Trade contact
Apator Mining Sp. z o.o.
Al. Roździeńskiego 188
40-203 Katowice, Poland
Head of Sales Department
Al. Roździeńskiego 188 40-203 Katowicefax +48 (32) 259-68-62Name:Krzysztof Skroch Function:Head of Sales Department Phone:+48 32 784 23 63 Mobile phone:+48 506 009 190 Fax:+48 32 259 68 62 |
Name:Marek Barbach Function:Sales Department Manager Phone:+48 32 784 23 62 Mobile phone:+48 507 129 151 |
Name:Jakub Smołka Phone:+48 32 784 23 57 Mobile phone:+48 507 129 151 |
Name:Korneliusz Kuczera Phone:+48 32 784 23 64 Mobile phone:+48 500 002 676 |