ZT-*45, ZTR-*45

The transformer units type ZT-*45 and ZTR-*45 are manufactured in flameproof housings and equipped with the main transformer for 4.5kVA power rating. The units type ZT-*45 are equipped with two independent contactor circuits (outputs) and make it possible to supply the installations (e.g. lighting ones) with three-phase voltage of 133V or 230V or control one or two lower power motors. The transformer units type ZTR-*45 are designed for reversible control of a motor with maximum power of 3kW. Voltage change of the transformer unit secondary side is performed by a user during its installation. The relays used make it possible to control the unit by connecting the standard control circuit (Roff < 600 Ω) and „low ohm" circuit (Roff < 100 Ω).

Technical data

Item
rated primary voltage
V
three-phase transfomer power
kVA
secondary voltage
V
outside auxiliary voltages with leak control
V
maximum power of connected motors
kW
rated current of discharge 133/230 V
A
loop-through terminals permissible load
A
overload protection adjustment range
A
overload protection adjustment range
A
Central leakage protection 133/230 V
Ω
Interlocking protection 133/230 V
Ω
Central interlocking 42V circuit protection
Ω
overall dimensions (width x height x depth)
mm
Weight
kg
catalogue number
-
certified with mark
-
certificate number
-
Item ZT-045 ZT-145 ZTR-045 ZTR-145
rated primary voltage
V
500, 50 Hz 1000, 50 Hz 500, 50 Hz 1000, 50 Hz
three-phase transfomer power
kVA
4,5+0,1Yy(d) 4,5+0,1Yy(d) 4,5+0,1Yy(d) 4,5+0,1Yy(d)
secondary voltage
V
133 (d) or 230 (y) 133 (d) or 230 (y) 133 (d) or 230 (y) 133 (d) or 230 (y)
outside auxiliary voltages with leak control
V
42, 50 Hz 42, 50 Hz 42, 50 Hz 42, 50 Hz
maximum power of connected motors
kW
1x3 or 2x1,5 1x3 or 2x1,5 1x3 1x3
rated current of discharge 133/230 V
A
19,5/11,3 19,5/11,3 19,5/11,3 19,5/11,3
loop-through terminals permissible load
A
180 180 180 180
overload protection adjustment range
A
1÷19,8 1÷19,8 1÷19,8 1÷19,8
overload protection adjustment range
A
3÷198 3÷198 3÷198 3÷198
Central leakage protection 133/230 V
Ω
7 7 7 7
Interlocking protection 133/230 V
Ω
15 15 15 15
Central interlocking 42V circuit protection
Ω
7 7 7 7
overall dimensions (width x height x depth)
mm
1070 x 785 x 540 1070 x 785 x 540 1070 x 785 x 540 1070 x 785 x 540
Weight
kg
240 240 240 240
catalogue number
-
AM-910047-03 AM-910047-06 AM-910066-03 AM-910066-06
certified with mark
-
CE 1453, I M2(M1) EX d [ia] I CE 1453, I M2(M1) EX d [ia] I CE 1453, I M2(M1) EX d [ia] I CE 1453, I M2(M1) EX d [ia] I
certificate number
-
KDB 05ATEX284X KDB 05ATEX284X KDB 05ATEX284X KDB 05ATEX284X

Information about types are available in catalogue.

Application

Transformer units are assigned for feeding electric mining tools and lighting circuits with a decreased three-phase voltage of 133V or 230 V.
Transformers units meet to requirements of the European Directive 94/9/EC (ATEX) for equipment in group I, category M2, and can be used in methane and coal dust exsplosion hazardous areas of underground mines.

Design

The tranformers units are made in a flameproof housing. Devices are fitted with protective devices against:
  • short circuits,
  • load asymmetry,
  • overload,
  • main channel low insulation resistance,
  • short circuits, high resistance and control circuit interruptions,
  • high earthing resistance
  • incorrect power voltage phase sequence (optionally).

Diagram

ZT-045, ZT-145

 

 

ZTR-045, ZTR-145  

 

 

Trade contact

Apator Mining Sp. z o.o.

 

Al. Roździeńskiego 188
40-203 Katowice, Poland

Head of Sales Department

Al. Roździeńskiego 188 40-203 Katowicefax +48 (32) 259-68-62
Name:Krzysztof Skroch
Function:Head of Sales Department
Phone:+48 32 784 23 63
Mobile phone:+48 506 009 190
Fax:+48 32 259 68 62
 
Name:Marek Barbach
Function:Sales Department Manager
Phone:+48 32 784 23 62
Mobile phone:+48 507 129 151
Name:Jakub Smołka
Phone:+48 32 784 23 57
Mobile phone:+48 507 129 151
Name:Korneliusz Kuczera
Phone:+48 32 784 23 64
Mobile phone:+48 500 002 676

Copyright © 2009-2010 Apator SA. All rights reserved.Created by VOBACOM