ARS 3
ARS vertical fuse switch disconnectors are designed for the distribution of electricity and protection against short circuits and overloads in three phase alternative current circuits. They are intended for direct installation on horizontal or vertical busbar systems. Their modern and compact design give much saving of space in substations and distribution boards. Each type is suitable for top cable terminal connection when installed on horizontal busbar system. Removal of the fuse link provides clearly noticeable, large isolating distance in the circuit. ARS vertical fuse switch disconnectors have making capacity in utilization categories: AC-21B, AC-22B, AC-23B. Easy installation of earthing devices is another advantage.
ARS vertical fuse switch disconnectors are designed to perform the following functions:
- protection
- distribution
- earthing
- switching
- touch protection.
All technical parameters required by standards and growing requirements of the market have been taken into account in design (conformity with EN 60947-3). Several advices and remarks from business partners have been also taken into account.
Technical data
| Item | |
Rated thermal current Ith |
A |
Rated voltage Un |
V |
Utilization category |
- |
Rated switching voltage Ue |
V |
Rated switching current Ie |
A |
Rated short circuit making current |
kA |
Rated short circuit withstand current |
kA |
Rated insulation voltage Ui |
V |
Rated short-circuit making capacity Uimp. |
kV |
Rated frequency |
Hz |
Mechanical durability |
- |
Electrical durability |
- |
Protection degree |
IP |
Weight |
kg |
Size of fuse links |
- |
| Item | ARS 3 | |
Rated thermal current Ith |
A |
630 |
Rated voltage Un |
V |
690 |
Utilization category |
- |
AC-22B |
Rated switching voltage Ue |
V |
690 |
Rated switching current Ie |
A |
630 |
Rated short circuit making current |
kA |
100 |
Rated short circuit withstand current |
kA |
100 |
Rated insulation voltage Ui |
V |
1000 |
Rated short-circuit making capacity Uimp. |
kV |
12 |
Rated frequency |
Hz |
50-60 |
Mechanical durability |
- |
1000 |
Electrical durability |
- |
200 |
Protection degree |
IP |
30 |
Weight |
kg |
2,5 |
Size of fuse links |
- |
3 |
Operating conditions
-
to be installed in the room free of any dust, aggressive or explosive gases,
-
altitude up to 2000 meters above sea level,
-
outdoor - in cabinets with protection degree > IP 34,
-
ambient temperature from -25°C to +55°C - but in case of use of disconnectors in temperature from +41°C to +45°C current value Ith should be reduced by 5% and within temperature range of +46°C to +55°C current value Ith should be reduced by 10%,
-
relative humidity of the air should not be higher than 50% at temperature of +40°C.
Versions
| Version | Designation | Part number |
|
| ARS 3 / 630 A | Switching of phases - single, cable terminal: M12 pressed nuts, cover for clamps
|
ARS 3-1-M | 63-811706-041 |
| ARS 3 / 630 A | Switching of 3 phases at the same time by handle, cable terminal, M12 pressed nuts, cover for clamps | ARS 3-6-M | 63-811707-041 |
| ARS 3 / 630 A | Switching of phases -single , V-shaped cable terminal, V- shaped cable, V-shaped terminal ring 70-300SW, cover for clamps | ARS 3-1-V | 63-811706-021 |
| ARS 3 / 630 A | Switching: 3 phases at the same time by one handle, V-shaped cable terminal, V-shaped clamping ring 70-300SW, cover for clamps | ARS 3-6-V | 63-811707-021 |
Clamps
| Designation of apparatus |
ARS 3-x-V (630 A) |
ARS 3-x-M (630 A) |
|
| Clamp | V-clamp 70 - 300SW | M- bolt clamp M12 (pressed nut) |
|
| Picture of clamp |
|
|
|
|
Cross-section of cable conductors
|
V-clamp to direct fixing of conductor with bare end with cross-section: |
cable terminal |
|
| |
|
||
| |
|
||
| Torque moment | 30 Nm | 56 Nm | |
| Bus bars of maximum width of 40 mm and maximum thickness of 8 mm can be fixed to cable clamps when isolating partition between phases is applied.
|
|||
Trade contact
Apator S.A.
ul. Żółkiewskiego 21/29,
87-100 Toruń, Poland
Foreign Trade Department Switchgear Equipment
Name:Rafał Kamiński Function:Area Sales Manager Phone:+48 (56) 6191 627 Mobile phone:+48 506 009 338 Information: Central Europe, The Balkans, Turkey (English) |
Name:Michael Roclawski Function:Area Sales Manager Phone:+48 (56) 6191 492 Mobile phone:+48 506 009 339 Information: Germany, Austria, Switzerland, Western Europe, Asia, Africa (German) |
Name:Grzegorz Błaszkiewicz Function:Logistics (Russian) Phone:+48 (56) 6191 316 Mobile phone:+48 506 009 374 |